Open Designer TCO Analysis →

MDCX Reference Design

200 Immersion Cooling Container (I200C20)

I200C20ST50

20ft 200 kW Immersion Cooling · 4× A32 tanks · up to 50 kW/tank · no UPS

Overview

What this SKU is: envelope, installed units, density, and the geometry you can download. Figures here are properties of the product, not of any one site.

ItemValueBasis
IT design load200 kWclaim C34
Installed units4claim C35
Maximum density50 kW/tankclaim C13
Air-cooled rack load5 kWtable MDCX immersion container specification
GPU capacity256table MDCX immersion container specification
Envelope6,058 × 2,438 × 3,490 mmtable ISO container envelope, MDCX module geometry
Footprint14.8 derived 6.058 m × 2.438 m
Lead time90 days ex-worksclaim C3

3D views

Orthographic and section views are generated from the published module geometry for this SKU. The interactive view is read-only — this is the standard configuration, not a configurator.

MDCX I200C20 immersion compute container cutaway
MDCX I200C20 immersion compute container cutaway

Geometry and schedules

No OpenUSD model is published for this SKU yet.

System boundary

The MDCX-supplied envelope is the container. Primary (utility) and secondary (facility) electrical sides meet at the transformer. Site responsibility begins at the published electrical and water interfaces.

Interface definition only. Implementation details are not published.

Power distribution

How power is broken down and distributed inside the boundary, and what the site must present at the connection point.

IT load against plant overhead

At: USA - Pennsylvania (PJM), 34 °C, Summer peak, 100% utilization. The racks draw below the density ceiling at this GPU — 15 kW of rack headroom remains.

Power distribution IT design load: 185 kW78.8%Plant overhead: 49.7 kW21.2%

Plant consumers

Plant consumers Tank CDU pumps6.8 kWDry cooler fans6.2 kWHybrid chiller30.5 kWDistribution loss1.9 kWFacility auxiliaries4.3 kW
ConsumerPowerShare of facility
IT — immersion tanks180 kW76.7%
IT — air-cooled rack5.0 kW2.1%
Tank CDU pumps6.8 kW2.9%
Dry cooler fans6.2 kW2.6%
Hybrid chiller30.5 kW13.0%
Distribution loss1.9 kW0.8%
Facility auxiliaries4.3 kW1.8%
Facility total235 kW100%

Plant overhead is 49.7 kW, 26.8% of IT, for a PUE of 1.268 at this point.

Single-line topology

Single-line topology (interface definition). Protection settings are not published.

Single-line topology GridTransformerMain switchIT-PDC2N — A / B feed×2Tank×4PDC1 (facility)

No UPS in this SKU — UPS and battery are customer-supplied, outside the container boundary.

Ratings at the boundary

Ratings in this section are derived from the IT design load and the published PUE band. They size an interface; they are not measured results and are not claims-registry facts. Each derived row prints its formula.

C12 immersion PUE ≈ 1.05 is peak dry-bulb ≤ 24 °C / free-cooling only. Hot-zone PUE is not 1.05.

ItemValueBasis
IT design load200 kWclaim C34
Facility load224–280.5 kWderived 200 kW × PUE 1.120–1.402
Connection capacity246.4–308.6 kWderived facility load × 1.10
Transformer capacity246.4–308.6 kWderived sized to connection capacity

Load schedule

A per-circuit load schedule is not published for this SKU. The topology above is the interface definition.

Interface definition only. Implementation details are not published.

Cooling distribution

How heat leaves the racks and reaches ambient: the loops, their design temperatures and flows, and where the plant switches from free cooling to mechanical cooling.

Heat distribution

At: USA - Pennsylvania (PJM), 34 °C, Summer peak, 100% utilization. The racks draw below the density ceiling at this GPU — 15 kW of rack headroom remains.

Heat distribution Dielectric coolant — direct immersion: 180 kW97.3%Air — auxiliary rack: 5.0 kW
Heat pathHeatShare of IT
Dielectric coolant — direct immersion180 kW97.3%
Air — auxiliary rack5.0 kW2.7%
IT heat total185 kW100%

97.3% of the heat leaves directly into the dielectric coolant; 2.7% is air from the auxiliary rack. There is no room-air cooling path to size.

Loop schematic

Cooling distribution oil 250 L/minprimary 32/37 °CImmersion tank35/43 °C×4Tank CDU2N×8Free cooler / hybrid chillerswitch at 24 °C

Loops

LoopSupplyReturnΔTDesign flowFluid
Tank oil loop — direct immersion35 °C43 °C8 K250 L/minSingle-phase dielectric coolant
Primary loop — CDU to heat rejection32 °C37 °C5 K125 L/min per CDU25% glycol

Heat rejection

Free cooling below the switch temperature; hybrid chiller above it

ItemValueBasis
CDU rated cooling400 kWtable MDCX immersion tank specification
CDU units installed8table MDCX immersion tank specification
In-row CRAH installedTBDTBD
In-row CRAH rated coolingTBDTBD
In-row CRAH fan powerTBDTBD
CDU secondary flow1,000 L/mintable MDCX immersion tank specification
CDU approachTBDTBD
Pressure drop35–45 kPatable MDCX immersion tank specification
Pipe diameterDN50table MDCX immersion tank specification
Switch temperature24 °Ctable MDCX heat-rejection selection rule

Interface definition only. Implementation details are not published.

Performance

PUE, WUE, and annual energy depend on site and workload, so they are not properties of the SKU. Solve this SKU at your own site:

Basis and disclaimer

Computed numbers in this document are operating-point results for the stated city, season, workload, and utilization. They are not guarantees or SLAs. Marketed numbers live in the claims registry.

Cited claims: C3 · C4 · C31 · C36 · C37 · C38 · C39 · C12 · C13 · C34 · C35.

C12 immersion PUE ≈ 1.05 is peak dry-bulb ≤ 24 °C / free-cooling only. Hot-zone PUE is not 1.05.

Expansion block and first delivery are 90 days ex-works from receipt of down payment (C3, C4); on-site installation and commissioning 3–4 weeks (C36). Freight and customs are buyer-arranged; MDCX publishes no estimate (C39). Retired schedule and fleet-PUE claims are not restated.

Reserved items

This document publishes what a correct result looks like. It does not publish how MDCX produces it, or with what.

WithheldStatement
BOM, makes, models, suppliersBill of materials, makes, models, and suppliers are not published.
Control logic, alarm thresholds, tuningControl logic, alarm thresholds, and tuning policy are not published.
Solver kernelThe solver kernel is not published. Operating conditions and result numbers are.
Manufacturing and quality path, taktManufacturing path, quality process, and line takt are not published.
Price and commercial termsPrice and commercial terms are not published.